Daikin FTXS20G2V1B Service Manual page 168

G-series
Hide thumbs Also See for FTXS20G2V1B:
Table of Contents

Advertisement

SiENBE04-808_A
Step
3. Remove the Titanium
apatite photocatalytic air-
purifying filter.
1
The Titanium apatite
photocatalytic air-
purifying filter ASSY is
attached to the back of
the air filter.
2
Remove the Titanium
apatite photocatalytic
air-purifying filter ASSY
by bending the air filter
and unfastening the
projections from the air
filter frame.
3
Remove the Titanium
apatite photocatalytic
air-purifying filter from
its frame (at 5 positions)
by bending it.
Removal Procedure
Procedure
Air filter
Titanium apatite
photocatalytic
air-purifying filter ASSY
Projections
Points
„ The Titanium apatite
photocatalytic air-purifying
filter is not marked for
difference between the right
and left sides.
(R7904)
(R7905)
(R4311)
Indoor Unit
156