Control Specification
3.4
Discharge Pipe Temperature Control
Outline
The discharge pipe temperature is used as the internal temperature of the compressor. If the
discharge pipe temperature rises above a certain level, the upper limit of frequency is set to keep
the discharge pipe temperature from rising further.
Details
Stop zone
Dropping zone
Keep zone
Up zone
Reset zone
A
B
C
D
E
50
B
C
D
Discharge pipe
temperature
Zone
When the temperature reaches the stop zone, the compressor stops.
The upper limit of frequency decreases.
The upper limit of frequency is kept.
The upper limit of frequency increases.
The upper limit of frequency is canceled.
09/12 class
(°C)
(°F)
(°C)
110
230.0
110
103
217.4
103
98
208.4
101.5
93
199.4
100
88
190.4
95
Control
18 class
(°F)
230.0
217.4
214.7
212.0
203.0
SiUS041829E
Stop zone
A
Dropping zone
Keep zone
Up zone
E
Reset zone
(R25005)
Part 4 Functions and Control