Troubleshooting by Remote Controller
4.19 Discharge Pipe Temperature Control
F3
Remote
Controller
Display
RZQG
Applicable
Models
The error is detected according to the temperature detected by the discharge pipe temperature
Method of Error
sensor.
Detection
When the discharge pipe temperature rises to an abnormally high level
Error Decision
When the discharge pipe temperature rises suddenly
Conditions
When the discharge pipe temperature does not rise after operation start
Defective discharge pipe thermistor
Supposed
Defective connection of discharge pipe thermistor
Causes
Refrigerant shortage
Defective compressor
Disconnection of discharge pipe thermistor
Defective outdoor unit PCB
150
ESIE15-13B
Service Diagnosis