Troubleshooting by Remote Controller
2.28 Discharge Pipe Temperature Control Error
F3
Remote
Controller
Display
Applicable
RZR, RZQ
Models
Method of Error
Abnormality is detected according to the temperature detected by the discharge pipe thermistor.
Detection
Error Decision
When the discharge pipe temperature rises to an abnormally high level
Conditions
When the discharge pipe temperature rises suddenly
When the discharge pipe temperature does not rise after operation start
Refrigerant shortage
Supposed
Defective compressor
Causes
Defective discharge pipe thermistor
Defective connection of discharge pipe thermistor
Disconnection of discharge pipe thermistor
Defective outdoor unit PCB
Service Diagnosis
SiUS281117
141