4.21 Electrical Box Temperature Rise

L3
Remote Control
Display
Method of
An electrical box temperature rise is detected by checking the radiation fin thermistor with the
Malfunction
compressor off.
Detection
„ With the compressor off, the radiation fin temperature is above
Malfunction
„ The error is cleared when the radiation fin temperature drops below
Decision
„ To cool the electrical components, the outdoor fan starts when the radiation fin temperature
Conditions
RK(X)S20-35G2V1B, ARXS20-35G2V1B
RK(X)S20-35G2V1B9, ARXS20-35G3V1B
RK(X)S42G2V1B, ARXS42G2V1B
RK(X)S50G2V1B, ARXS50G2V1B
„ Defective outdoor fan motor
Supposed
„ Short circuit
Causes
„ Defective radiation fin thermistor
„ Disconnection of connector
„ Defective outdoor unit PCB
Service Diagnosis
rises above
°C and stops when it drops below
Troubleshooting
°C.
°C.
°C.
(°C)
(°C)
(°C)
80
70
80
98
75
83
80
70
75
95
80
85
134