Control Specification
3.6

Freeze-up Protection Control

Outline
During cooling operation, the signal sent from the indoor unit controls the operating frequency
limitation and prevents freezing of the indoor heat exchanger. (The signal from the indoor unit is
divided into zones.)
Detail
The operating frequency limitation is judged with the indoor heat exchanger temperature.
3.7

Heating Peak-cut Control

Outline
During heating operation, the indoor heat exchanger temperature determines the frequency
upper limit to prevent abnormal high pressure.
Detail
53
(Reference)
13°C
Reset zone
9.5°C
Up zone
7.5°C
Keep zone
5.5°C
Drooping zone
0°C
Stop zone
°C
°C
°C
Indoor heat exchanger
thermistor temperature
Zone
Stop zone
When the temperature reaches the stop zone, the compressor stops.
Drooping zone
The timer starts, and the frequency is drooping.
Keep zone
The upper limit of frequency is kept.
Up zone
The upper limit of frequency is increased.
Reset zone
The upper limit of frequency is canceled.
20/25/35 class
(°C)
65
(°C)
56
(°C)
53
(°C)
51
(°C)
46
Indoor heat exchanger
thermistor temperature
42 class
50 class
65
65
55
56
54
55
52
53
50
51
SiENBE04-808_A
Stop zone
°C
Drooping zone
Keep zone
Up zone
°C
Reset zone
(R11819)
Control
Function and Control
(R4561)