Malfunctions - Daikin FTXS20G2V1B Service Manual

G-series
Hide thumbs Also See for FTXS20G2V1B:
Table of Contents

Advertisement

Control Specification

3.12 Malfunctions

3.12.1 Sensor Malfunction Detection
Sensor malfunction may occur in the thermistor.
Relating to Thermistor Malfunction
1. Outdoor heat exchanger thermistor
2. Discharge pipe thermistor
3. Radiation fin thermistor
4. Outdoor temperature thermistor
3.12.2 Detection of Overcurrent and Overload
Outline
An excessive output current is detected and, the OL temperature is observed to protect the
compressor.
„ If the OL (compressor head) temperature exceeds 120 ~ 130°C (depending on the model),
Detail
„ If the inverter current exceeds 9.25 ~ 20 A (depending on the model), the system shuts down
3.12.3 Refrigerant Shortage Control
Outline
I Detecting by power consumption
If the power consumption is below the specified value and the frequency is higher than the
specified frequency, it is regarded as refrigerant shortage.
The power consumption is small comparing with that in the normal operation when refrigerant is
insufficient, and refrigerant shortage is detected by checking a power consumption.
II Detecting by discharge pipe temperature
If the discharge pipe temperature is higher than the target discharge pipe temperature, and the
electronic expansion valve is fully open for more than the specified time, it is regarded as
refrigerant shortage.
III Detecting by the difference of temperature
If the difference between suction and discharge temperature is smaller than the specified value,
it is regarded as refrigerant shortage.
Refer to "Refrigerant shortage" on page 140 for detail.
59
the system shuts down the compressor.
the compressor.
Refrigerant shortage zone
48 ~ 55 Hz
Frequency
(depending on
the model)
(R12184)
Target discharge
pipe temperature
Refrigerant shortage
zone
(R1391)
SiENBE04-808_A
Function and Control

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents