4.22 Radiation Fin Temperature Rise
L4
Remote Control
Display
Method of
A radiation fin temperature rise is detected by checking the radiation fin thermistor with the
Malfunction
compressor on.
Detection
If the radiation fin temperature with the compressor on is above
Malfunction
The error is cleared when the radiation fin temperature drops below
Decision
If the error repeats, the system is shut down.
Conditions
Reset condition: Continuous run for about 60 minutes without any other error
RK(X)S20-35G2V1B, ARXS20-35G2V1B
RK(X)S20-35G2V1B9, ARXS20-35G3V1B
RK(X)S42G2V1B, ARXS42G2V1B
RK(X)S50G2V1B, ARXS50G2V1B
Defective outdoor fan motor
Supposed
Short circuit
Causes
Defective radiation fin thermistor
Disconnection of connector
Defective outdoor unit PCB
Silicon grease is not applied properly on the radiation fin after replacing the outdoor unit
Service Diagnosis
PCB.
°C.
°C.
(°C)
(°C)
90
85
98
78
92.5
85
105
99
Troubleshooting