SiENBE04-808_A
4.17 Position Sensor Abnormality
H6
Remote Control
Display
Method of
A compressor start-up failure is detected by checking the compressor running condition through
Malfunction
the position detection circuit.
Detection
If the error repeats, the system is shut down.
Malfunction
Reset condition: Continuous run for about 11 minutes (50 class: 5 minutes) without any
Decision
Conditions
Disconnection of the compressor relay cable
Supposed
Defective compressor
Causes
Defective outdoor unit PCB
Start-up failure caused by the closed stop valve
Input voltage is out of specification
Service Diagnosis
other error
Troubleshooting
126