5.1

Overview

For the products sold in European countries, the conformance to the EMC Directive, which is one of the European
Directives, has been a legal obligation since 1996.
In addition, conformance to the Low Voltage Directive, another European Directive, has also been a legal obligation since
1997.
Manufacturers, who recognize that their products comply with the EMC Directive and the Low Voltage Directive, must
declare that their products comply with the Directives and put a CE mark on the products.
■1. Sales representative in Europe
The sales representative in Europe is as shown below.
Company name: Mitsubishi Electric Europe BV
Address: Gothaer strase 8, 40880 Ratingen, Germany
5.1.1

Conforming standards in the EMC Directive

The GOT complies with the following standards in the EMC Directive.
Applied
standard
CISPR16-2-3
Radiated noise
CISPR16-2-1
Conducted noise
IEC61000-4-2
Electrostatic immunity
IEC61000-4-3
Radiated electromagnetic
field, amplitude modulation
IEC61000-4-4
EN61131-2
: 2007
Fast transient burst noise
IEC61000-4-5
Surge immunity
IEC61000-4-6
Conducted RF immunity
IEC61000-4-8
Power supply frequency
magnetic field immunity
5 - 2
5.1 Overview
Test standard
Test for measuring electromagnetic
*1
emissions from the product
Test for measuring electromagnetic
emissions from the product to the
*1
power cables
Immunity test in which static electricity
is applied to the cabinet of the
*1
equipment
Immunity test in which an electric field
is applied to the product
*1
Immunity test in which burst noise is
applied to the power cables and the
*1
signal lines
Immunity test in which lightening surge
*1
is applied to the product
Immunity test in which a noise
inducted on the power cable and the
*1
signal lines is applied
Test for checking normal operations
under the circumstance exposed to the
ferromagnetic field noise of the power
supply frequency (50/60 Hz)
Test details
• 30 MHz to 230 MHz
• 230MHz to 1000MHz
• 150kHz to 500kHz
• 500kHz to 30MHz
• Contact discharge: ±4 kV
• Aerial discharge: ±8 kV
80 MHz to 1000 MHz: 10 V/m
1.4GHz to 2GHz: 3V/m
2.0GHz to 2.7GHz: 1V/m
(80% amplitude modulation at 1 kHz)
Power cable: 2 kV
Digital I/O (24V or higher): 1kV
Digital I/O (less than 24 V): 250 V or
higher
Analog I/O (signal lines): 250 V or
higher
• AC power type
• DC power type
Power cable: 10V
Data communication port: 10 V
30 A/m
Standard value
QP: 30 dBμV/m (measured at 30
*2*3
m)
QP: 37 dBμV/m (measured at 30
*2*3
m)
*2
QP: 79dB,Mean: 66dB
*2
QP: 73dB,Mean: 60dB
Power cable (between cable and
ground): ±2 kV
Power cable (between cables): ±1 kV
Data communication port: ±1 kV
Power cable (between cable and
ground): ±0.5kV
Power cable (between cables):
±0.5kV
Data communication port: ±1 kV