Single Boiler, Room Sealed Flue - REMEHA Quinta 115 Technical Information

High-efficiency condensing boiler for wall mounted installation output: 18 - 115 kw
Hide thumbs Also See for Quinta 115:
Table of Contents

Advertisement

Quinta 115
maximum Length L
Eq. Length bend 45°
Eq. Length bend 90°
Table 13 Calculation data conventional flue
Example: Quinta 115, total length 15 m, 2 bends 45°.
15 m + 2 x 1.4 = 17.8 < 19: flue Ø 100mm OK.
Note: If the design parameters are outside the values shown in the above table or
there is any doubt over the flue system, please contact our technical department for
calculation to be undertaken.

7.3.5 Single boiler, room sealed flue

Fig. 08
Flue gas discharge duct without bends, single boiler, room sealed
application.
04.W4H.79.00003 + 04.W4H.79.00005
Ø 100 mm
m
19
m
1.4
m
4.9
Remeha Quinta 115
Ø 125 mm
34
74
1
1,7