maximum Length L
Eq. Length bend 45°
Eq. Length bend 90°
Table 14 Calculation data room sealed applications
Example: Quinta 115, total length 3 m, 1 bends 45°.
3 m + 1 x 2 = 5 m < 7 m: flue OK.
Note: If the design parameters are outside the values shown in the above table or
there is any doubt over the flue system, please contact our technical department for
calculation to be undertaken.
7.3.6 Different pressure zones
Fig. 09
Different pressure zones
04.W4H.79.00004
Ø 100/150 mm
m
7
m
2
m
3
35
Flue outlet