Flow Temperature Set Point (!); Pump Run On Time Htg (@) - REMEHA Quinta 115 Technical Information

High-efficiency condensing boiler for wall mounted installation output: 18 - 115 kw
Hide thumbs Also See for Quinta 115:
Table of Contents

Advertisement

6.5.1 Flow temperature set point (!)

The required flow temperature is adjustable from 20 to 90°C.
Fig. 04
Typical setting change procedure
110397_5

6.5.2 Pump run on time HTG (@)

Pump run on time can be adjusted (Please refer to installation contractor)
- Press the 'm' -key until the digit ! (with dot) appears in the 'code'-display.
- Press the 's'-key until the digit @ (with dot) appears in the 'code'-display.
- Set the required value, using the [+] and [-]-keys.
- Press the 'e'-key to store the new value (value will flash twice).
- Press the 'reset'-key to return to operating mode.
NOTE: For continuous pump operation use manual override, see Par. 6.1.3.
Code
t
@
00
@
Xx
Table 07 Pump run on time HTG
Description
Pump runs on for 10 seconds
Pump runs on for 1 to 15 minutes (xx = 01 to 15)