Single Boiler, Room Sealed Flue - REMEHA Quinta 45 Technical Information

Table of Contents

Advertisement

max eq. Length L
eq. Length bend 45°
eq. Length bend 90°
Table 13 Calculation data conventional flue
Example: Quinta 65, total length 15 m, 2 bends 90°.
15 m + 2 x 4.9 = 24.8 < 27: flue OK.
Note: If the design parameters are outside the values shown in the above table or
there is any doubt over the flue system, please contact our technical department for
calculation to be undertaken.

7.3.5 Single boiler, room sealed flue

Fig. 08
Flue gas discharge duct without bends, single boiler,
room sealed application.
04W4H7900003 and 04W4H7900005
55979.indd 36
55979.indd 36
Quinta 45
80 mm
m
33
m
1.2
m
4
36
Remeha
Quinta 45/65
Quinta 65
100 mm
27
1.4
4.9
2-4-2009 9:42:39
2-4-2009 9:42:39