8
ELECTRICAL INSTALLATION
8.1 General
The Remeha Quinta 115 is supplied as standard with electronic control and flame
ionisation safety controls with a specially designed microprocessor at the heart of the
control system.
8.2 Specifications
8.2.1 Electrical supply
The Remeha Quinta 115 must have a permanent 230V-50Hz single phase supply
rated at 6.3 A. The control unit is not phase / neutral sensitive.
8.2.2 Control box
Supply voltage:
Electrical rating:
Pre-purge time:
Post-purge time:
Safety time:
Anti-hunting time:
Pump run on (HTG):
Pump run on (DHW):
8.2.3 Fuse specification
The boiler is protected by fuses:
- On the main power supply located in
the euro connector socket rated at 6.3
A (slow acting). Spare fuse is supplied
- located in the euro connector socket
- Control circuit 230 V - located on the
control box, ref. F1 rated at 2 A (fast
acting)
- Control circuit 24 V dc- located on the
control box, ref. F2 rated at 4 A (slow
acting)
Spare fuses are supplied - located on the
control box cover.
230 V/50 Hz
10 VA
4.2 seconds
10 seconds
4.2 seconds maximum
min. 150 seconds
1 - 15 minutes
5 minutes
42
Remeha Quinta 115
��
��
��
��
��� �����
��
Fig. 12
Control box
00.W4H.79.00018
NOTE: Do not use connector X8!
�������������
��
��� �����
��
��