NOTE: The full load adjustment changes the gas/air graph slope angle, whilst the part
load adjustment shifts the base point on a parallel axis; each adjustment therefore
alters the previous setting slightly. Repeat the process 18 a. to 18 e. and re-check the
values as many times as necessary until they fall into values as in Table 16.
19. Remove flue gas analyser and seal test point; also remove manometer and re-
tighten test nipple and test for soundness.
20. Simulate a lock out condition by turning off gas cock, the boiler will attempt to fire
4 times, on the 5
lock out codes. Re-set the boiler using the reset key.
21. Re-fit boiler front panel and close grey panel
22. Allow boiler to run up to its set flow temperature, see Par. 6.5.1 and shut off
23. When pumps have stopped, check water pressure is correct
24. The boiler is now ready for use
25. Check system controls
26. Set system controls to required values
Complete commissioning sheet, recording boiler serial No and site details and return
copy to Broag for record purposes
NOTE: The Remeha Quinta 115 is supplied with a number of factory default settings
which should be correct for most installations. If other setting values are required refer
to Par. 6.5 and 6.6.

9.2 Shut-down

9.2.1 Temporary shut-down with frost protection

- Do not isolate the electric power supply.
- Do not close the gas cock.
- Use the switch function, see Par. 6.1.3.

9.2.2 Permanent shut-down without frost protection

- Set system controls to off.
- Isolate the electric power supply.
- Close the gas cock.
attempt the boiler will lock out on flashing 0@, see Table 19 ;
th
53