Fault Codes - REMEHA Quinta 115 Technical Information

High-efficiency condensing boiler for wall mounted installation output: 18 - 115 kw
Hide thumbs Also See for Quinta 115:
Table of Contents

Advertisement

6
With the Celcia
MC4 or another
OpenTherm
controller: Check
the communication
between controller
and boiler with the aid
of the 'code' window
and t window on
the control panel
00.W4H.79.00044
7
Investigate boiler
settings and wiring
Table 18 Fault-finding

10.2 Fault codes

In the event of an error message, both the 'code'-display and the t-display will flash.
For details, see Table 19.
For readout of the most recent faults, see Par. 6.9.
IMPORTANT:
Before resetting, accurately record the fault code (including figures, flashing digits and
dots) and remember to pass on this information when seeking assistance. The fault
code is important for correctly and rapidly tracing the nature of the fault.
NOTE: Shut-off mode (code b, only dots in t-display are flashing, not digits) is a
normal boiler operating function and does not represent a boiler failure. However,
this may indicate a system problem, an internal fan check or an incorrect parameter
setting.
Under the normal
operating condition,
press the m key for 2
seconds: does the top
part not flash in the
'code' window?
Under the normal
operating condition,
press the m key for 2
seconds: does the top
part not flash in the t
window?
Is nothing flashing??
Check the parameter
settings of the boiler
Check the wiring on the
boiler terminal strip and
to the control box
55
Communication
(connection) with the
control unit is not in order
or the control unit is
defective
Communication with the
controller is not in order
or the control unit is
defective
or the controller is
defective
Replace the control unit
If all is correct, replace
the control box.