Remeha Avanta Plus
600 mm
S
G
S
F
B
P
A
H
G
fig. 16
Flue terminal positions
R000150
Roof mounted
room sealed
terminal
L
112952LTGBW7H065b
112952.LT.GB.W7H.065
L
80/125 or 60/100
112952.LT.GB.W7H.066
112952LTGBW7H066a
table 03
Maximum pipe lengths for flue duct and air supply in room sealed application
127768-271011
R
No flue must penetrate
area within dotted lines
600 mm
round roof light
2000 mm
D,E
C
M
J
L
J
K,N
Diameter in mm Ø
Maximum length 'L' allowed [m]
Eq. Length of 90° elbow
LT W6H 000 031
Eq. Length of 45° elbow
LTNLW6H000031A
LT W6H 000 032
LTNLW6H000032A
Positions for the Remeha Avanta Plus are shown in the figure
and table 02.
Dimen-
Terminal location
sions
A
Directly below an opening, air brick,
opening window, etc.
B
Above an opening, air brick, open-
ing window, etc.
C
Horizontally to an opening, air brick,
opening window, etc.
D
Below a gutter or sanitary pipe work
E
Below the eaves
F
Below a balcony or carport roof
G
Above ground, roof or balcony level
H
From vertical drain/soil pipe work
J
From an internal or external corner
R000150-A
K
From a surface or boundary facing
the terminal
L
Vertically from a terminal on same
wall
M
Horizontally from a terminal on
same wall
N
From a terminal facing the terminal
P
From an opening in a carport (e.g.
door, window) into the building
R
From a vertical structure on the roof
S
Above an intersection with the roof
table 02
Minimum distances to terminal
n/a = not applicable.
2.5.2

Room sealed flue

See table 03 for the maximum pipe length of flue ducts and air
supply pipes for this 'room sealed' application.
It is not necessary to provide combustion air to the room or
internal space in which the boiler is installed.
18s/24s/30s
60/100 80/125 60/100 80/125 60/100 80/125 60/100 80/125
6
29
24c/28c
35c
6
29
7
30
1.4
0.65
2. Installation
Minimum dis-
tance to ter-
minal (room
sealed)
300 mm
300 mm
300 mm
75 mm
200 mm
200 mm
300 mm
150 mm
300 mm
1500 mm
1500 mm
300 mm
1200 mm
1200 mm
n/a
300 mm
39c