REMEHA Quinta 115 Technical Information page 52

High-efficiency condensing boiler for wall mounted installation output: 18 - 115 kw
Hide thumbs Also See for Quinta 115:
Table of Contents

Advertisement

Fig. 20
Flue gas measure point.
05.W4H.79.00004
Fan speed
Checking value
Setting value
Table 16 Checking and setting data H-gas (with open air case)
Fan speed
Checking value
Setting value
Table 17 Checking and setting data L-gas (with open air case)
NOTE: When checking combustion the C0
Table 16 and Table 17. If the levels are outside these tolerances adjustment to the
levels must be made in accordance with the tolerance in Table 16 and Table 17.
18 e. Check ionisation level on full and part load, measurement in volts between
terminal 4 and earth max 9 volts min 4 volts DC,
see Fig. 21 (measurment is linear 1V dc =1µA dc).
full load
7000 rpm
O
%
4,7 ± 0,5*
2
CO
%
9,1 ± 0,3*
2
O
%
2
CO
%
2
full load
7000 rpm
O
%
4,3 ± 0,5*
2
CO
%
9,3 ± 0,3*
2
O
%
2
CO
%
2
n/a
n/a
n/a
n/a
levels should be in accordance with the
2
52
Remeha Quinta 115
part load
1300 rpm
4,3 ± 0,5
9,3 ± 0,3
4,3 ± 0,2
9,3 ± 0,1
part load
1300 rpm
4,3 ± 0,5
9,3 ± 0,3
4,3 ± 0,2
9,3 ± 0,1
� ���� ���� ������