Single Boiler, Room Sealed Flue - REMEHA Quinta 30 Technical Information

High-effi ciency condensing boiler
Table of Contents

Advertisement

7.3.5 Single boiler, room sealed flue

Fig. 08
Flue gas discharge duct without bends, single boiler, room sealed
application.
04.W3H.79.00005 + 04.W3H.79.00006
max eq. Length
eq. Length bend 45°
eq. Length bend 90°
Table 14 Calculation data room sealed applications
Example: Quinta 30, total length 10 m, 2 bends 90°.
80 mm: 10 m + 2 x 4 = 18 m < 20 m: flue OK.
Note: If the design parameters are outside the values shown in the above table or
there is any doubt over the flue system, please contact our technical department for
calculation to be undertaken.
57117.indd 34
57117.indd 34
Quinta 30
80/125 mm
m
20
m
1.2
m
4
34
Remeha Quinta 30
1-4-2009 14:35:52