7.3.5 Single boiler, room sealed flue

Fig. 08 Flue gas discharge duct without bends, single boiler, room sealed application
04.W3H.79.00005 + 04.W3H.79.00006
max eq. Length
eq. Length bend 45°
eq. Length bend 90°
Table 14
Calculation data room sealed applications
Example: Quinta 30, total length 10 m, 2 bends 90°.
80 mm: 10 m + 2 x 4 = 18 m < 20 m: flue OK.
Note: If the design parameters are outside the values shown in the above table or
there is any doubt over the flue system, please contact our technical department for
calculation to be undertaken.
Quinta 30
80/125 mm
m
20
m
1.2
m
4
34