Read-Out Mode (X00); Fan Speed Mode (<00) - REMEHA Quinta 115 Technical Information

High-efficiency condensing boiler for wall mounted installation output: 18 - 115 kw
Hide thumbs Also See for Quinta 115:
Table of Contents

Advertisement

End point (10 V): adjustable between +51°C and (( (+299)°C .
This value sets the required flow temp at 10 V signal input (restricted by the max flow
set point).
NOTE: These settings are only applicable when boiler control operation parameter
(A) has the x value set to 4.

6.7 Read-out mode (X00)

To check boiler set points and values.
Using the 'm'-key, press repeatedly until !(flashing dot) appears in the 'code'-display.
Then select the required code @, # or $ etc. using the 's'-key.
Code
Description
Actual flow temperature
!
Actual return temperature
@
Actual DHW temperature
#
(only with sensor connected)
Actual outdoor temperature
$
(only with sensor connected)
n/a
%
Flow temperature (set point)
^
Actual heat demand status
&
Calculated HTG cut-in temperature
*
Actual flow temperature rise [0.1 °C/sec]
(
n/a
A
Table 10 Read-out mode user level
6.8 Fan speed mode (<00)
Using the 'm' -key, press repeatedly until 'code'-display shows alternate flashing half
digits.
The value in the t-display shows the actual fan speed using two alternate double
digits as table:
Remeha Quinta 115
28
Read-out
(example)
80
70
58
05
3&
80
1x = demand;
0x = no demand
67
02