maximum Length L
eq. Length bend 45°
eq. Length bend 90°
Table 13 Calculation data conventional flue
Example: Quinta 85, total length 15 m, 2 bends 45°.
15 m + 2 x 1.4 = 17.8 < 24: flue OK.
Note: If the design parameters are outside the values shown in the above table or
there is any doubt over the flue system, please contact our technical department for
calculation to be undertaken.

7.3.5 Single boiler, room sealed flue

Fig. 08
Flue gas discharge duct without bends, single boiler, room sealed application.
04.W4H.79.00003 + 04.W4H.79.00005
Quinta 85
100 mm
m
24
m
1.4
m
4.9
34