Remeha Quinta 115
The boiler flow temperature is boosted to the DHW set point + DHW control stop set
point (see Par. 6.6.7 and 6.6.10).
When the DHW sensor or thermostat is satisfied the boiler turns off. The control
turns off the DHW pump and turns on the system pump (provided there was still a
HTG demand. If no HTG demand, the selected pump will run on for a maximum of 5
minutes).
A Broag high output indirect calorifier can be connected to the Remeha Quinta 115 in
accordance with the schematic sketch shown (see Fig. 10).
Fig. 10
Remeha Quinta with calorifier and DHW pump