4 Electrical wiring
Terminal board 2
Mark
Item
Name
1
L1
P.S.: Power supply (necessary):
The mains power supply connection (230 Vac) is wired to terminals L1 and N.
2
N
3
1
4
2
EXP. VALVE: Expansion valve connection (necessary):
5
3
Link to expansion valve assembly. Number links from 1 to 6 must match in e-box
6
4
terminal board and expansion valve terminal board
7
5
8
6
9
-
-
Not used
10
-
11
L
MD: Motor Drain discharge (optional):
A drain water pump (field supplied) can be connected to DX-kit interface.
12
N
FAN CONTROL: Fan tap speed control by HITACHI remote controller (optional):
13
N
N-Neutral phase connection (common)
14
H
H: High fan speed signal
15
M
M: Medium fan speed signal
16
L
L: Low fan speed signal
17
-
-
Not used
18
-
M. AL: Motor alarm signal:
19
1
Alarm input signal can be used for alarm link between the DX-Kit interface and the
unit connected. If the jumper between terminal 1 (19) and 2 (20) is open, unit will be
20
2
switched to alarm condition. Connect again to restart the system
N O T E
• • (*1): Locked rotor amperage (LRA) must be lower than 8A.
• • (*2): Alarm signal with high voltage (1~ 230V 50Hz): Connection in M.AL. terminals is mandatory. In case
that motor alarm detection were not necessary, make sure to connect the harness jumper provided with the
DX-Interface.
Expansion valve box
Mark
Item
Name
1
1
2
2
Control connection (necessary):
3
3
Link to control assembly. Number links from 1 to 6 must match in
4
4
expansion valve terminal board and control terminal board.
5
5
6
6
154
SMGB0077 rev.0 - 01/2013
Description
Description
Wire and maximum
current specifica-
tion (EN60335-1)
1~230V 50Hz, Max
current. 5A
Wire section:
3x0,75mm2
Wire section:
6x0,5mm2
-
1-230V 50Hz Max
current: 1A (output)
Wire section:
2x0,75mm2
Maximum current
allowed: 3,5A
Wire section:
4x0,75mm2
(*1)
-
Wire section:
2x0,75mm2
(*2)
Wire and maximum current
specification (EN60335-1)
Wire section: 6x0,5mm2

Hide quick links: