12 Maintenance notes
Consumables
Consumable
Cleaning product
Adhesive tape
Piece of felt

12.1.2 Indoor cleaning


Cleaning the built-in 4-way indoor unit RCI(M)
Preliminary procedure.
Place a vinyl sheet on the floor to protect the furniture and other items from the cleaning water before starting this job.
Remove the optional air panel as indicated in section Removal of the optional air panel.
Remove the electrical box after opening the corresponding panel and then disconnect the connectors located between the
indoor and outdoor units and other connectors, as indicated in sections Removal of the electrical box cover and Removal
of the electrical box.
Remove the bellmouth and fan as indicated in section Removal of the fan duct and the fan.
Remove the drain pan as indicated in sections Removal of the drain pan and Removal of the drain pan. Also carry out the
following tasks:
1 Remove the drain pan after emptying it of water.
2 Empty the drain pan of water by removing the rubber plug. Make sure the water flows easily through the hole by inser-
ting a pencil into it.
3 Once the drain pan has been removed, check that there is no water in the drainage at the bottom of the pan.
4 Clean and dry the pan before removing it. Handle the pan carefully.
Remove the float switch as indicated in sections Removal of the float switch and Removal of the float switch.
Cleaning the indoor unit
N O T E
Wear gloves to avoid injuries caused by the heat exchanger fins.
Place a vinyl sheet around the heat exchanger to prevent the cle-
aning water from splashing the insulation surface and drain pump.
404
SMGB0077 rev.0 - 01/2013
Remarks
Neutral soap
To secure the vinyl sheeting so that the room is protected from
the cleaning water
Diameter of 120 mm