10 Servicing
1
2
3
4
5
Remove the rear cover as indicated in chapter Removal of the inlet
and outlet air thermistor.
Remove the tape located in the centre of the casing.
Press the locks and remove half of the fan casing.
Remove the fixture support screws and carefully remove the motor together with the fans.
Loosen the screws securing the fans to the motor shaft.
N O T E
If the fan casing is to be fully removed, remove the screws securing the other half to the fan motor fixture.

10.6.5 Removal of the drain mechanism

1
N O T E
To disconnect and remove the drain mechanism, previously
see the chapter corresponding to the wiring diagrams in this
Manual.
Remove the drain pump support screws and remove it.
1
2
3
N O T E
Prior to installing the new pump:
1
Remove the electrical box from the unit to connect it to
the printed circuit board (PCB) in line with the instructions
given in chapter Removal of the electrical box.
2 Seal the drain hose gaskets correctly.
351
SMGB0077 rev.0 - 01/2013
Part
Locks
Duct
Fixture supports
Fan motor
Fan casing
Part
Drain pump
Part