Refrigerant And Drain Hose Installation; Rci - 4-Way Cassette (1.0-6.0)Fsn3 - Hitachi RCI-1.0FSN3 Service Manual

Indoor units system free series & complementary systems fsn(h)(2/3/4)(e/m)(i)(-du)
Table of Contents

Advertisement

3 Piping work and
refrigerant charge

3.5 Refrigerant and drain hose installation


General notes
Dimensions of the flare and thickness of the copper pipe
Nominal diameter
mm
inches
Ø6.35
1/4
Ø9.52
3/8
Ø12.70
1/2
Ø15.88
5/8
Dimensions of the flare nuts for flared connections
Nominal diameter
mm
inches
Ø6.35
1/4
Ø9.52
3/8
Ø12.70
1/2
Ø15.88
5/8

3.5.1 RCI - 4-way cassette (1.0-6.0)FSN3


Refrigerant pipe installation
The correct position for the refrigerant pipe connection is shown below. The pipe connection must be accessible from all
directions
(above, left or right).
102
SMGB0077 rev.0 - 01/2013
Thickness
Measurement A
mm
0.80
9.1
0.80
13.2
0.80
16.6
1.00
19.7
Measurement B mm
17
22
26
29
(Gas pipe)
95
160
(Liquid pipe)
/
+ 0
- 0.4 mm
(mm)
φ30