12 Maintenance notes
KPI-(502-1002)H3E
Aluminium heat exchanger can be cleaned using vapour. Clean
the exchager using stream.
12.1.4 Collection of refrigerant to replace the indoor unit
Collection of refrigerant after replacing the indoor unit
1 Connect the gauge manifold to the gas and liquid stop valve.
2 Switch the power supply ON.
3 Enable pin 1 of DSW1 on the outdoor unit PCB for cooling ope-
ration. Close the liquid stop valve and collect the refrigerant.
4 Carry out the following procedures immediately when the side
pressure drops and the gas stop valve indicates –0.01 MPa.
N O T E
Prevent the pressure from dropping below –0.01 MPa. If the
pressure is less, the compressor may be faulty.
a. Close the gas stop valve.
b. Disable pin 1 of DSW1.
5 Switch off the power supply.