3 Piping work and
refrigerant charge
Prepare a polyvinyl chloride (PVC) pipe with an outer diameter of
32 mm.
Fasten the tubing to the drain hose with an adhesive and the
factory-supplied clamp. The drain piping must be performed with a
down-slope pitch of 1/25 to 1/100.
Insulate the drain pipe after connecting the drain hose.
NOTE
If the relative humidity of the inlet air or the ambient air
exceeds 80% in the place where the unit is installed, fit an
auxiliary drain pan (field-supplied) below the indoor unit, as
indicated in the figure.

3.5.7 RPI - Ducted indoor unit (2.0-6.0)FSN4E


Refrigerant pipe installation
The correct position for the refrigerant pipe connection is shown below.
114
SMGB0077 rev.0 - 01/2013
Indoor unit
RPI-(2.0-6.0)
1
4
3
2
1
Gas pipe
2
Liquid pipe
3
Drain hose
4
Electrical box
Auxiliary drain pan
(field-supplied)
2
4
1
RPI-(8.0/10.0)
3