3 Piping work and
refrigerant charge
Models
RCI-(1.0/1.5)FSN3Ei
RCI-2.0FSN3Ei
RCI-(2.5–6.0)FSN3Ei

Drain pipe installation
The correct position for the drain hose connection -A- is shown below.
Prepare a polyvinyl chloride (PVC) pipe with an outer diameter of 32 mm.
Secure the pipe with the clamp and adhesive supplied.
The drain hose must have a gradient of 4% (1/25) to 1% (1/100).
Clamp (accessory)
Do not use adhesive
Drainage pipe
connection
Drainage pipe
(accessory)
C A U T I O N
Do not apply too much force when making the drain hose connection as this could damage it.
Do not use bent or twisted drain pipes as these will cause water leaks.
Then insulate the drain hose appropriately.
105
SMGB0077 rev.0 - 01/2013
(1) Gas pipe mm (inches)
Ø12.70 (1/2)
Ø15.88 (5/8)
A
4% (1/25) - 1% (1/100)
PVC pipe Ø 32
(field-supplied)
Use PVC adhesive
(2) Liquid pipe mm (inches)
Ø6.35 (1/4)
Ø9.52 (3/8)
Clamp (accessory)
Insulation
(field-supplied)