Hitachi RCI-1.0FSN3 Service Manual page 247

Indoor units system free series & complementary systems fsn(h)(2/3/4)(e/m)(i)(-du)
Table of Contents

Advertisement

6 Optional functions
C9 – Not available
CA – Not available
Cb – Selection of forced stoppage logic
This function determines the operating logic for the forced stoppage contacts.
The setting conditions and contact logic are shown in the following table:
Setting
00
01
CC – Not available
Cd – Not available
CE – Not available
CF – Change of louver swing angle
This function is useful when the louver swing angle (air discharge
angle) must be changed.
Setting condition
00
01
02
d1 – Power supply ON/OFF 1
This function stores the unit settings in the event of a power cut. The unit is restarted when the power is re-established.
C A U T I O N
When this function is used without anyone controlling the unit, set the system monitoring mode to avoid risks.
N O T E
In the event of an electrical fault, the unit starts and stops according to the on/off setting of the power supply. If
the fault occurs during a stoppage enabled through the remote control, the unit will restart automatically once the
power supply is reconnected.
d2 – Not available
235
SMGB0077 rev.0 - 01/2013
Setting condition
Contact
Contact logic
Contact A
Normally open
Contact B
Normally closed
Louver swing angle
Approx. 30 to 60°
Approx. 30 to 50°
Approx. 40 to 60°
Activation contact
Open
Normal
Forced stoppage
Forced stoppage
Closed
Normal
6