Mounting Position - Mitsubishi GOT1000 GT15 User Manual

Graphic operation terminal
Hide thumbs Also See for GOT1000 GT15:
Table of Contents

Advertisement

6.3 Mounting Position

When mounting the GOT, the following clearances must be left from the other device.
C
Type
GOT only or bus
connection unit
Bus connection unit
serial communication
unit fitted
RS-422 Conversion
unit is fitted
Ethernet
A
communication unit,
MELSECNET/10
communication unit
(coaxial), CC-Link
communication unit
fitted.
MELSECNET/10
communication unit
(optical) fitted.
B
C, D
E
*1
For GT15-75QBUSL, GT15-75QBUS2L, GT15-75ABUSL, or GT15-75ABUS2L only
*2
For GT15-QBUS, GT15-QBUS2, GT15-ABUS, or GT15-ABUS2 only
The values enclosed in parenthesis apply to the case where no other equipment generating radiated noise
(such as a contactor) or heat is installed. However, keep the ambient temperature of the GOT to 55°C or
lower even in such a case.
The required lead-in allowance for cables may be larger than the size of A above depending on the unit or
cable used.
For the lead-in allowance for cables at the bottom of the GOT, refer to the following.
Appendix 1 External Dimensionss
D
GT1595
50(1.97) or more
*1
[20(0.79) or more]
fitted
*2
or
50(1.97) or more
[20(0.79) or more]
50(1.97) or more
50(1.97) or more
[20(0.79) or more]
E
Panel thickness: 2 to 4mm
(0.08 to 0.16inch)
GT157
GT1585
50(1.97) or more
[31(1.22) or more]
50(1.97) or more
[31(1.22) or more]
51(2.01) or more
68(2.68) or more
50(1.97) or more
[20(0.79) or more]
50(1.97) or more
50(1.97) or more
[26(1.02) or more]
[43(1.69) or more]
80 or more (20 or more)
50 or more (20 or more)
100 or more (20 or more)
6.3 Mounting Position
1
2
3
GT156
50(1.97) or more
4
[36(1.92) or more]
50(1.97) or more
[36(1.42) or more]
73(2.87) or more
5
6
50(1.97) or more
[48(1.89) or more]
7
Unit: mm (inch)
8
6
- 2