8.7 Battery
Battery is used to backup data when the power supply of GOT is OFF.
The data which can be backed-up with the battery is shown below.
• Present time (Clock data) (
• Maintenance time notification data (
8.7.1
Applicable battery
The following battery is applicable for GT15
Model
GT15-BAT
8.7.2
Battery specifications
Item
Type
Initial voltage
Nominal current
Storage life
Total power stoppage time
Lithium content
Application
8.7.3
Battery replacement procedure
Replace battery periodically by referring to Section 8.7.4 Battery life.
1
Keep the GOT power supply on for 10 minutes or more, and
turn it off. (Executes step
powering the GOT power supply off.)
2
Remove the battery holder form the GOT backside.
3
Remove the old battery from the holder and disconnect the
connector.
4
Connect the new battery to the connector.
5
Insert the battery into the holder and set it into the GOT
backside.
6
Turn the GOT power supply on.
7
Check if the battery condition is normal within the utility.
Refer to the following for the details of battery status display.
8
8.7 Battery
- 21
8.7.1 Applicable battery
12.1 Time Setting and Display)
Battery for backup of clock data and maintenance timing setting data.
Magnesium manganese dioxide lithium primary battery
Approx.5 years (Operating ambient temperature of 25°C)
For backup of clock data and maintenance timing setting data.
to
within 5 minutes of
6
12. CLOCK SETTINGS AND BATTERY STATUS DISPLAY (TIME SETTING AND
DISPLAY)
16.1 Maintenance Timing Setting)
.
Description
Specifications
3.0V
1800mAh
Refer to Section 8.7.4 Battery life
0.49g
BATTERY
Battery holder
(GOT rear face)