Maintenance Time Notification Function - Mitsubishi GOT1000 GT15 User Manual

Graphic operation terminal
Hide thumbs Also See for GOT1000 GT15:
Table of Contents

Advertisement

16.1 Maintenance Timing Setting

16.1.1 Maintenance time notification function

When use maintenance time notification function, battery and option function button are required.
When setting the maintenance notifying time, refer to the life descrived in Section 3.2 Performance
Specifications as a guide to set time or count.
The maintenance time notification is output by the following two methods.
• Outputs to GOT special register (GS680).
• Outputs as system alarm
For details of the GOT special register and system alarm, refer to the following.
GT Designer2 Version
Switching OFF the maintenance time notification output
Item
Sets energization time for the maintenance
Backlight
notification output.
maintenance time
When 0, no message notification.
notification period.
The time is counted only when backlight is lit,
(0 to 100000 hour)
in every ten minutes.
Sets energization time for the maintenance
Display section
notification output.
maintenance time
When 0, no message notification.
notification period
The time is counted only when energized, in
(0 to 100000 hour)
every ten minutes.
Touch key
Sets touch key touching count for the
maintenance time
maintenance notification output.
notification count
When 0, no message notification.
Counts by every screen touch.
(0 to 2000000times)
Sets built-in flash memory writing count for the
Built-in flash memory
maintenance notification output.
maintenance time
When 0, no message notification.
notification count
Counts by every writing in built-in flash
(0 to 1000000times)
memory.
By using system alarm, the message that notifies that the maintenance time is near or it is already
maintenance time is displayed.
For the display of the system alarm, refer to the following.
20. ERROR MESSAGE AND SYSTEM ALARM
For the display of the system alarm, refer to the following.
GT Designer2 Version
Screen Design Manual
The maintenance time notification setting which has been set once is not switched
OFF even if changing its setting.
Switch OFF the maintenance time notification by the following methods.
• Execute addition time reset.
• Switch OFF each bit of "maintenance time notification cancel information
(GS638)".
Description
Screen Design Manual
Setting range
0 to 100
<At factory
shipment: 0>
0 to 100
<At factory
shipment: 0>
0 to 200
<At factory
shipment: 0>
0 to 200
<At factory
shipment: 0>
16.1 Maintenance Timing Setting
16.1.1 Maintenance time notification function
10
11
12
Maintenance
points
Unit
Reference
page
13
1000
18-5
hours
1000
14
hours
10000
times
15
1000
times
16
16
- 2
9

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Got1000Gt15

Table of Contents