Selecting any of the monitoring items "load meter" and "cumulative energization time"
When the "load meter" has been selected, the output current monitor screen is switched to a
corresponding screen. When the "cumulative energization time" has been selected, the output
voltage monitor screen is switched to a corresponding screen. When any of these three items has
been selected, the output current or output voltage monitor screen cannot be used.
When "load meter" rnoni-
When the kurnulative energiza-
tor has been selected,
tion t l r n e h o n i t o r has been se-
Flrst priorlty screen
this screen is switched.
'-----------------'
0
MONITOR
---
STOP
EXT
STOP EXT
+
I
I
I
I
I
(SHI F T)
I
I
L----------
(Selective rnonttor)
(Alarm
code monltor)
Selecting "current monitoring" o r "power monitoring"
Note that a current not more than 5% of the rated current of the inverter cannot be detected and
displayed.
Also note that the electronic thermal relay does not operate at that current. For motor protection,
examine the use of an external temperature detector or the like.
Example: When a small motor (0.4kW motor) is run by a large-capacity inverter (55kW), power
monitoring is inactive.