Mitsubishi Electric Freqrol-A100 Instruction Manual page 205

Freqrol-a100 series transistorized inverter for variable torque loads
Table of Contents

Advertisement

7.2.2
Inboard Dedicated Options
Out of the above option units, only one can be installed in the inverter.
Each option unit has several function as listed above.
PLG feedback control
r =
Option
FR-EPB
(Computer l i n k
function)
Function
12-bit digital input
Relay output (3 points)
FR-EPC
(Programmable
controller l i n k
functlon)
0
0
P L G f e e d b a c k control
1 2 - b ~ t d ~ g t a l l n p u t
R e l a y o u t p u t
Extensron a n a l o g o u t p u t
C o m p u t e r l m k
M E L S E C N E T I M I N I - S 3
P I control
P r o g r a m m e d operation
A n a l o g c u r r e n t o u t p u t
Pulse t r a i n i n p u t
Extension analog output
Analog current output
0
Computer link function
(serial communication)
FR-EPD
(Automatic
control
compatible
function)
0
FR-EPE
(110 function)
0
0
0
Function, Application, Etc.
Rating, Etc.
this detection signal is fed back to the inverter, and
its speed variation is automatically compensated for.
Hence, the
Weed can be kept
if load
variation occurs.
The actual motor speed can be monitored on the in-
verter LED display and parameter unit.
[Application example] extruder, winder, conveyor,
etc.
lnput interface used to set the inverter frequency ac-
curately using external BCD or binary digital signals.
Either 12-bit binary or BCD 3-digit signal can be se-
lected.
FR-EPG
(Computer link
+
extension
output function)
0
0
0
The motor speed is detected by the pulse encoder,
1 .
Speed variation ratio: within f0.2% at the load varia-
tion of 0 to 100% (') (at 1800rlmin)
.
Applicable motor: standard motor of 2 to 8 poles
.
Encoder specifications: 3 phase, differential output,
1024Plrev.
.
5VDC power supply
Example: Tamagawa Seiki's TS 1508
N 207, etc.
(*)
Load of 100% indicates the continuous operation
torque of the motor at each running frequency.
lnput voltage, current: 24VDC. 5mA (per circuit)
.
Input signal format: contact signal input or transistor
open collector (sink type) input
Example: MELSEC AY40, AY4OA, etc.
Gain and offset can also be adiusted.
.
Any three signals can be selected and output as re-
lay contacts,(change-over contacts) from among the
10 standard output signals (RUN, SU, IPFIUVT, OL,
FU1, FU2, RBP, THP, PRG, PU) of the inverter.
The FR-EPG and EPH have one point of relay
outout.
FR-EPH
(Pulse train
input function)
0
0
0
.
Signal types: change-over contact (three output re-
lays installed)
.
Contact capacity: 230VAC 0.3A
3OVDC 0.3A
16 signals, which can be monitored on the FM and
AM terminals, such as output frequency, output volt-
age, output current and motor torque, are expanded
and output.
A 1mA DC or
sv
(I O V)
DC meter can be connected.
(FR-EPE)
A 20mADC or 5V(IOV)DC meter can be connected.
(FR-EPG, EPH terminals AMO. AMI)
Gain and offset can also be adiusted.
Allows inverter operationlmonitoring and parameter
readlwrite to be performed using user program from
a computer, e.g. personal computer or FA controller,
which is connected by communication cables.
Noiseless communication system using twisted pair
cables.
Allows inverter operationlmonitoring and parameter
readlwrite to be performed using user program from
the master station in the Mitsubishi programmable
controller data link system MELSECNETIMINI-S3
(AJ71PT3243) which is connected by optical fiber.
Communication is made via optical link system with-
out noise.
.
Output voltage across LMO-LM2
0 to IOVDC,
I
across AMO-AMC
1:
max. 1 mA
.
output current across LMI-LM2
0 to 1mADC
(
across AMl-AMC
1:
(2OmA)
Output resolution: 3mV for voltage output
Output resolution: 1pA for current output (20pA)
Output accuracy ? l o %
.
Conforming standard: EIA Standard, for RS-422 and
RS-485
r
Transmission format: multidrop link system
.
Communication speed: max. 19200 baud rates
Max. number of inverters
:
RS-422
-
10 Inverters
connected
RS-485
-
32 inverters
.
Overall extension: 500m
.
Max. number of inverters connected: 16 inverters
(up to 64 inverters when used with remote 110 sta-
tions)
.
Interstation transmission distance: 50m max.
1 m min