Mitsubishi Electric Freqrol-A100 Instruction Manual page 211

Freqrol-a100 series transistorized inverter for variable torque loads
Table of Contents

Advertisement

External Dimensions (Unit: mm
Terminal block
Ter
L
Note:
Note:
The numeral ir
the type indi-
cates a motor
capacity (kW).
Use the FR-
BAL
AC
reac-
tor for inverter
capacities of
0.4K to 3.7K.
Fig.
1
Fig. 2
L
D
Mounting hole
Terminal block-
(mounting screw F)
Specification number
' 4
V)
a
-
..
Serial number
0
0
Wlrlng, Etc.
l n p u t
power
factor: a b o u t
95%
n
lnverter
I
FR-EEL
Disconnect link.
r1ote:l. The input power factor is im-
proved to about
95
%.
2.
The link across inverter termi-
nals P and P I must be discon.
nected.
(If it is not disconnected, there
is no power factor improve-
ment.)
3. The wiring distance from the
inverter should be within 5m.
4.
The size of the cable used
should be identical to or larger
than that of the power supply
cable (R, S, T). (See page 167.
5.
Select the reactor according tc
the motor capacity. (If the in-
verter capacity is greater than
the motor capacity, select the
reactor according to the motor
capacity .)
l n p u t p o w e r factor: a b o u t
90%
lote: 1. The input power factor is im-
proved to about
90%.
2.
Select the reactor according to
the motor capacity. If the in-
verter capacity is greater than
the motor capacity, select the
reactor according to the motor
capacity.
3. Use the reactor for
22
kW
when a 18.5 K inverter is used