Mitsubishi Electric Freqrol-A100 Instruction Manual page 93

Freqrol-a100 series transistorized inverter for variable torque loads
Table of Contents

Advertisement

Pr. 29
-
Pr.
30
Prevention of cargo collapse on
conveyor, etc.
rsxzi~z
set
"2" to provide an
s
-
~
~
~
~
ac-
[S-pattern accelerat~onldecelerat~~n
B]
celerationldeceleration from f2
(current frequency) to f l (target
frequency), easing an accelera-
tionldeceleration shock. This pat-
t
tern has an effect on the preven-
tion of cargo collapse, etc.
Backlash compensation for reduction gear, etc.
Set " 3 " . This function stops the output frequency change tem-
porarily during acceleration/deceleration, reducing a shock
(backlash) generated when a reduction gear backlash is elimi-
nated suddenly. Use Pr.
33
to 36 for the setting.
acrory
I
I
I
'
mange
I
dettlng
I
Set value 31
I
Backlash
I
I
[Backlash compensation function]
A
acceleration
/
stopping
I
o
120Hz
I
I
frequency
I
I
I
Backlash
I
I
1
frequency
1
I
I
Note: When Pr. 29
= 3,
Pr. 33 to 36 act as parameters for backlash
compensation function. Frequency jump function, if used, for
Pr. 33 to 36 will still function but parameter values are not
shown. To read these parameters set Pr. 29
= 0,
1 or 2.
36
and used wi'ih t'he inverter, the inverter must be protection-
coordinated with the high power factor converter. When
connecting the high power factor converter, always set any
of 3, 4 and 5 in Pr.
30.
Also, connect cables between the
inverter, power supply and high power factor converter
correctly in accordance with the high power factor con-
verter instruction manual.
(1) lnverter operation enable signal input terminal
The inverter operation enable (RDY) signal of the high
power factor converter is entered into this terminal. Allocate
the used terminals to the MRSIAUIRT terminal by parame-
ter setting and connect it to the RDY terminal of the high
power factor converter (refer to Table 1). The conventional
functions of the used terminals are deleted (refer to Table
2).
Operation logic
lnverter operation enable signal input
terminal and SD are connected
.............
Output shut-off
lnverter operation enable signal input
terminal and SD are disconnected
.........
Shut-off canceled
The operation logic is fixed. Unlike the mechanical reset
(MRS) signal, it cannot be changed by parameter setting.
Backlash
decelerat~on
stopplng time
O
360 seconds
OS Seconds