4.6.2
External Signal-Based Operation Mode Switching Function
-
- -
Setting method
Set "8" in Pr. 79 "operation mode selection".
External signal-based opera-
The input signal RH is assigned as the external signal-based
tion mode switching signal
operation mode switching signal. (When "8" is set in Pr. 79, RH
automatically operates as the external signal-based operation
mode switching signal.)
Functions
In the external signal-based operation mode switching mode,
the following functions are made valid:
Set
Value
I
1
t is connected
1
PU operation mode
1
the external operation
I
1
8
Connection of RH and SD in the PU operation mode forces the
inverter to switch to the external operation mode. Disconnection
of RH and SD switches the inverter to the PU operation mode.
Note that this switching can be done only during an inverter stop
Terminals
RH and SD
and cannot be done diring operation.
-
Note: 1. Setting "8" in Pr. 79 changes the function of terminal
RH (three-speed setting (high speed)) to the opera-
tion mode switching function. At this time, the function
of terminal RH (three-speed setting (high speed)) is
invalid.
2. This function is not available for the FR-PUO1 E para-
meter unit.
Connected
Fixed Mode
Remarks
External operation mode
Cannot be switched to
the PU
eration mode.
Cannot be switched to