Mitsubishi Electric Freqrol-A100 Instruction Manual page 213

Freqrol-a100 series transistorized inverter for variable torque loads
Table of Contents

Advertisement

Specifications, Structure, Etc.
Note:l
.
This panel cannot be installed
on the inverter. Use this panel
with the parameter unit cable.
2.
Installation method
Operation panel
3. Acceptable plate thickness
4.
Parameters cannot be read or
written.
Panel cut diagram
5. IP65 protection
[Unit: mm]
This filter suppresses a surge voltage generated in the motor terminal
voltage when a 400V class motor is driven by. the inverter.
Terminal
MountFg toot
- .
screw J
-
E
Inverter
FA-ASF
2q-H-b
4
4 -
W
W
lote: 1. Connect the cables from the out-
put terminals (U. V, W) of the in-
verter to the input terminals (U,
V, W) of the filter and the cables
from the motor terminals to the
output terminals (X, Y,
Z)
of the
filter. Run the cables with ex-
treme care. Incorrect wirina may
overheat and damaae the resis-
tor.
2.
The wiring length from the in-
verter output terminals to the fil-
ter input terminals should be
within 5m.
3. The wiring length from the filter
terminals to the motor terminals
should be within 300m.
4.
The terminals used for wiring
should be sleeved solderless
terminals.