4.7.3

Acceleration/deceleration pattern (Pr.29, Pr.140 to Pr.143)

You can set the acceleration/deceleration pattern suitable for application.
You can also set the backlash measures that stop acceleration/deceleration once at the parameter-set
frequency and time during acceleration/deceleration.
Parameter
Number
29
Acceleration/deceleration pattern
selection
140
Backlash acceleration stopping frequency
141
Backlash acceleration stopping time
142
Backlash deceleration stopping frequency
143
Backlash deceleration stopping time
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 175)
....
Specifications differ according to the date assembled. Refer to page 322 to check the SERIAL number.
Setting value "0"
[Linear acceleration
/ deceleration]
Time
Setting value "1"
[S-pattern acceleration
/deceleration A]
fb
Time
CAUTION
⋅ As the acceleration/deceleration time of S-pattern acceleration/deceleration A, set the time taken until Pr. 3 Base frequency
is reached, not Pr. 20 Acceleration/deceleration reference frequency.
Setting value "2"
[S-pattern acceleration
/deceleration B]
f1
f2
Time
Setting value "3"
[Anti-backlash measure
function]
Pr. 140
Pr. 13
Pr. 143
Pr. 141
Name
(1) Linear acceleration/ deceleration (Pr. 29 = "0", initial value)
⋅ When the frequency is changed for acceleration, deceleration, etc. in inverter
operation, the output frequency is changed linearly (linear acceleration/
deceleration) to reach the set frequency without straining the motor and
inverter. Linear acceleration/deceleration has a uniform frequency/time slope.
(2) S-pattern acceleration/deceleration A (Pr. 29 = "1")
⋅ For machine tool spindle applications, etc.
Used when acceleration/deceleration must be made in a short time to a high-
speed range of not lower than the base frequency. In this acceleration/
deceleration pattern, Pr. 3 Base frequency (fb) is the inflection point of the S
pattern and you can set the acceleration/deceleration time appropriate for motor
torque reduction in a constant-power operation range of base frequency (fb) or
higher.
(3) S-pattern acceleration/deceleration B (Pr. 29 = "2")
⋅ For prevention of load shifting in conveyor and other applications. Since
acceleration/deceleration is always made in an S shape from current
frequency (f2) to target frequency (f1), this function eases shock produced
at acceleration/deceleration and is effective for load collapse prevention,
etc.
(4) Backlash measures (Pr. 29 = "3", Pr. 140 to Pr. 143)
⋅ What is backlash?
Reduction gears have an engagement gap and have a dead zone between
forward rotation and reverse rotation. This dead zone is called backlash, and
this gap disables a mechanical system from following motor rotation.
More specifically, a motor shaft develops excessive torque when the
Pr. 142
direction of rotation changes or when constant-speed operation shifts to
deceleration, resulting in a sudden motor current increase or regenerative
status.
⋅ To avoid backlash, acceleration/deceleration is temporarily stopped.
Time
Set the acceleration/deceleration stopping frequency and time in Pr. 140 to
Pr. 143.
Setting of acceleration/deceleration time
and acceleration/deceleration pattern
Initial
Setting
Value
Range
0
Linear acceleration/ deceleration
1
S-pattern acceleration/deceleration A
2
S-pattern acceleration/deceleration B
0
3
Backlash measures
Variable-torque acceleration/
6
deceleration
1Hz
0 to 400Hz
Set the stopping frequency and time
0.5s
0 to 360s
for backlash measures.
1Hz
0 to 400Hz
Valid when Pr. 29 = 3
0.5s
0 to 360s
Description