Mitsubishi Electric FR-F720-0.75K to 110K Instruction Manual page 172

Table of Contents

Advertisement

Inverter
Forward
STF
rotation
Voltage/current
input switch
SD
4
0 to 5VDC
10
Frequency
2
setting
5
Connection diagram using
terminal 2 (0 to 5VDC)
Inverter
Forward
STF
Voltage/current
input switch
rotation
SD
4
0 to 10VDC
10E
Frequency
2
setting
5
Connection diagram
using terminal 2 (0 to 10VDC)
Inverter
Forward
rotation
STF
Terminal 4
AU
input selection
SD
DC0 to 5V
10
Frequency
4
setting
5
Connection diagram
using terminal 4 (0 to 5VDC)
Forward
STF
rotation
AU
SD
4 to 20mADC
Current
4
Frequency
input
setting
equipment
5
Connection diagram using
terminal 4 (4 to 20mADC)
Forward
STF
rotation
SD
4 to 20mADC
Current
2
Frequency
input
setting
equipment
5
Connection diagram using
terminal 2 (4 to 20mADC)
(2) Perform operation by analog input voltage
⋅ The frequency setting signal inputs 0 to 5VDC (or 0 to 10VDC) to across
the terminals 2-5. The 5V (10V) input is the maximum output frequency.
The maximum output frequency is reached when 5V (10V) is input.
2
⋅ The power supply 5V (10V) can be input by either using the internal
power supply or preparing an external power supply. The internal power
supply outputs 5VDC across terminals 10-5, or 10V across terminals
10E-5.
Terminal
10
10E
2
⋅ When inputting 10VDC to the terminal 2, set any of "0, 2, 4, 10, 12, 14"
in Pr. 73. (The initial value is 0 to 5V)
⋅ Setting "1 (0 to 5VDC)" or "2 (0 to 10VDC)" in Pr. 267 changes the
terminal 4 to the voltage input specification. When the AU signal turns
on, the terminal 4 input becomes valid.
Voltage/current
input switch
REMARKS
4
2
The wiring length of the terminal 10, 2, 5 should be 30m maximum.
(3) Perform operation by analog input current
Inverter
⋅ When the pressure or temperature is controlled constant by a fan, pump,
etc., automatic operation can be performed by inputting the output signal
Voltage/current
input switch
4 to 20mADC of the adjuster to across the terminals 4-5.
4
2
⋅ The AU signal must be turned on to use the terminal 4.
⋅ Setting any of "6, 7, 16, 17" in Pr. 73 changes the terminal 2 to the
Inverter
current input specification. At this time, the AU signal need not be turned
Voltage/current
input switch
on.
4
2
Frequency setting by analog input (terminal 1, 2, 4)
Inverter Built-in Power
Frequency Setting
Supply Voltage
Resolution
5VDC
0.030Hz/60Hz
10VDC
0.015Hz/60Hz
Pr. 73 (terminal 2
input voltage)
0 to 5VDC input
0 to 10VDC input
4
163