Appendix 1-2 Replacement Of The Fr-A100 <Excelent> Series; Instructions For Installation - Mitsubishi Electric FR-F720-0.75K to 110K Instruction Manual

Table of Contents

Advertisement

(4) Main differences and compatibilities with the FR-F500(L) series
Item
Simple mode parameters 61
Pr. 0 Torque boost initial value
11K to 55K: 2%
User group 1 (16), user group 2 (16)
(Pr. 160, Pr. 173 to Pr. 175)
User initial value setting (Pr. 199)
Changed/cleared
DC injection brake function with terminal (X13
functions
signal)
(Pr. 11 setting value 8888, Pr. 180 to Pr. 186 setting
value 13)
Long wiring mode
(Pr. 240 setting 10, 11)
Intelligent optimum acceleration/deceleration
(Pr. 60 setting "3" and Pr. 61 to Pr. 63)
Automatic torque boost
(Pr. 38, Pr. 39)
Performing parameter clear and all clear (H5A96,
HAA99) with the FR-A7ND clears Pr. 345 and Pr. 346.
Terminal block
Removable terminal block
PU
FR-PU04, DU04
Computer link, relay output option
Plug-in option
FR-A5NR
Three boards can be mounted
Installation size
Appendix 1-2 Replacement of the FR-A100 <EXCELENT> series

Instructions for installation

• When using the installation holes of the FR-A100(E) series, FR-A5AT (intercompatibility attachment) is necessary.
For customers who are replacing the conventional model with this inverter
FR-F500(L)
Dedicated plug-in option (not compatible)
FR-F720-0.75K, 2.2K, 3.7K, 7.5K, 18.5K, 22K, 37K, 45K,
FR-F740-0.75K to 3.7K, 7.5K, 22K, 37K to 55K are compatible in mounting dimensions
For other capacities, an optional intercompatibility attachment (FR-AAT) is necessary.
FR-F700
Simple mode parameters 15
Pr. 0 Torque boost initial value
initial value
11K to 37K: 2%, 45K, 55K: 1.5%
(When the torque boost value of the FR-F500 series used
was the initial value, it is not necessary to change the
torque boost value from the initial value when replacing
with the FR-F700 series.)
User group (16) only
Setting methods were partially changed
(Pr. 160, Pr. 172 to Pr. 173)
"User initial value setting" (Pr. 199) was cleared
Substitutable with the copy function of the operation panel
(FR-DU07)
DC injection brake function with terminal was cleared
Start in reverse rotation is possible with flying start function
(frequency search of automatic restart after instantaneous
power failure function)
Setting is not necessary
(Pr. 240 settings "10" and "11" were cleared)
Function was cleared
For deceleration time, overvoltage fault can be avoided
with regeneration avoidance function (Pr. 882 to Pr. 885).
Automatic torque boost was cleared because of addition of
"Simple magnetic flux vector" (Pr. 80)
Pr. 345 and Pr. 346 are not cleared.
Removable terminal block
Upward compatibility (Terminal block of the F500 can be
mounted)
FR-PU07
FR-DU07
FR-DU04 unavailable (Partly restricted when the FR-PU04
is used. Refer to page 312.)
Built into the inverter
(RS-485 terminal, relay output 2 points)
One board can be mounted
313

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents