Control Circuit Terminal Layout - Mitsubishi Electric FR-F720-0.75K to 110K Instruction Manual

Table of Contents

Advertisement

2.3.3

Control circuit terminal layout

SE
(1) Common terminals of the control circuit (SD, 5, SE)
Terminals SD, 5, and SE are all common terminals (0V) for I/O signals and are isolated from each other. Do not
earth(ground) these terminals.
Avoid connecting the terminal SD and 5 and the terminal SE and 5.
Terminal SD is a common terminal for the contact input terminals (STF, STR, STOP, RH, RM, RL, JOG, RT, MRS, RES,
AU, CS) and frequency output signal (FM).
The open collector circuit is isolated from the internal control circuit by photocoupler.
Terminal 5 is a common terminal for frequency setting signal (terminal 2, 1 or 4) and analog output terminal AM.
It should be protected from external noise using a shielded or twisted cable.
Terminal SE is a common terminal for the open collector output terminal (RUN, SU, OL, IPF, FU).
The contact input circuit is isolated from the internal control circuit by photocoupler.
(2) Signal inputs by contactless switches
The contacted input terminals of the inverter (STF, STR, STOP,
RH, RM, RL, JOG, RT, MRS, RES, AU, CS) can be controlled
using a transistor instead of a contacted switch as shown on the
right.
A1
B1
C1
A2
B2
C2 10E 10
RL
RM
RH
RT
AU
STOP
RUN
SU
IPF
OL
FU
SD
2
5
4
MRS
RES
SD
FM
AM
1
SD
STF
STR
JOG
CS
PC
External signal input using transistor
Control circuit specifications
Control circuit terminal
Terminal screw size: M3.5
Tightening torque: 1.2N.m
+24V
STF, etc
Inverter
SD
2
31

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents