Speed Does Not Accelerate; Unable To Write Parameter Setting; Power Lamp Is Not Lit - Mitsubishi Electric FR-F720-0.75K to 110K Instruction Manual

Table of Contents

Advertisement

Check first when you have a trouble

5.5.12 Speed does not accelerate

Check
points
Start command and frequency command are chattering.
Input
The wiring length used for analog frequency command
signal
is too long, and it is causing a voltage (current) drop.
Input signal lines are affected by external EMI.
Pr. 1, Pr. 2, Pr. 18, calibration parameter C2 to C7 settings
are improper.
Torque boost (Pr. 0, Pr. 46) setting is improper under V/F
control, so the stall prevention function is activated.
Parameter
V/F pattern is improper when V/F control is performed.
Setting
(Pr. 3, Pr. 14, Pr. 19)
Stall prevention function is activated due to a heavy
load.
During PID control, output frequency is automatically controlled to make measured value = set point.

5.5.13 Unable to write parameter setting

Check
points
Input
Operation is being performed (signal STF or STR is
signal
ON).
You are attempting to set the parameter in the External
operation mode.
Parameter is disabled by the Pr. 77 Parameter write
Parameter
selection setting.
Setting
Key lock is activated by the Pr. 161 Frequency setting/key
lock operation selection setting.
Operation mode and a writing device do not
correspond.

5.5.14 Power lamp is not lit

Check
points
Main
Circuit,
Wiring or installation is improper.
Control
Circuit
278
Possible Cause
Possible Cause
Possible Cause
Countermeasures
Check if the start command and the frequency
command are correct.
Perform analog input bias/gain calibration.
Take countermeasures against EMI, such as using
shielded wires for input signal lines.
Check the settings of Pr. 1 Maximum frequency and Pr. 2
Minimum frequency. If you want to run the motor at 120Hz
or higher, set Pr. 18 High speed maximum frequency.
Check the calibration parameter C2 to C7 settings.
Increase/decrease Pr. 0 Torque boost setting value by
0.5% increments so that stall prevention does not occur.
Set rated frequency of the motor to Pr. 3 Base frequency.
Use Pr. 19 Base frequency voltage to set the base voltage
(e.g. rated motor voltage).
Change Pr. 14 Load pattern selection according to the load
characteristic.
Reduce the load weight.
Set Pr. 22 Stall prevention operation level higher according
to the load. (Setting Pr. 22 too large may result in
frequent overcurrent trip (E.OC ).)
Check the capacities of the inverter and the motor.
Countermeasures
Stop the operation.
When Pr. 77 = "0" (initial value), write is enabled only
during a stop.
Choose the PU operation mode.
Or, set Pr. 77 = "2" to enable parameter write regardless
of the operation mode.
Check Pr. 77 Parameter write selection setting.
Check Pr. 161 Frequency setting/key lock operation selection
setting.
Check Pr. 79, Pr. 338, Pr. 339, Pr. 550, Pr. 551, and select
an operation mode suitable for the purpose.
Countermeasures
Check for the wiring and the installation.
Power lamp is lit when power supply is input to the
control circuit (R1/L11, S1/L21).