Frequency setting by analog input (terminal 1, 2, 4)
⋅ Refer to the following table and set Pr. 73 and Pr. 267. (
Terminal 2
Pr. 73
Setting
Input
0
0 to 10V
1
0 to to 5V
(initial value)
2
0 to 10V
3
0 to 5V
4
0 to 10V
5
0 to 5V
6
0 to 20mA
7
0 to 20mA
10
0 to 10V
11
0 to 5V
12
0 to 10V
13
0 to 5V
14
0 to 10V
15
0 to 5V
16
0 to 20mA
17
0 to 20mA
0
1
(initial value)
2
3
4
0 to 10V
5
0 to 5V
6
7
10
11
12
13
14
0 to 10V
15
0 to 5V
16
17
⋅ Set the voltage/current input switch referring to the table below.
Terminal 2 Input
Specifications
Voltage input (0 to 10V)
0, 2, 4, 10, 12, 14
Voltage input (0 to 5V)
1 (initial value), 3, 5, 11, 13, 15
Current input (0 to 20mA)
6, 7, 16, 17
indicates an initial value.
CAUTION
⋅ Turn the AU signal on to make terminal 4 valid.
⋅ Match the setting of parameter and switch. A different setting may cause a fault, failure or malfunction.
⋅ The terminal 1 (frequency setting auxiliary input) signal is added to the main speed setting signal of the terminal 2 or 4.
⋅ When an override is selected, the terminal 1 or 4 is used for the main speed setting and the terminal 2 for the override signal
(50% to 150% at 0 to 5V or 0 to 10V). (When the main speed of the terminal 1 or terminal 4 is not input, compensation by the
terminal 2 is made invalid.))
⋅ Use Pr. 125 (Pr. 126) (frequency setting gain) to change the maximum output frequency at input of the maximum output frequency
command voltage (current). At this time, the command voltage (current) need not be input.
Also, the acceleration/deceleration time, which is a slope up/down to the acceleration/deceleration reference frequency, is not
affected by the change in Pr. 73 setting.
⋅ When Pr. 22 Stall prevention operation level = "9999", the value of the terminal 1 is as set to the stall prevention operation level.
162
Terminal 4 Input
Terminal 1
AU
Input
signal
0 to ±10V
0 to ±10V
0 to ±5V
0 to ±5V
0 to ±10V
0 to ±5V
0 to ±10V
0 to ±5V
Off
0 to ±10V
0 to ±10V
0 to ±5V
0 to ±5V
0 to ±10V
0 to ±5V
0 to ±10V
0 to ±5V
0 to ±10V
0 to ±10V
0 to ±5V
0 to ±5V
According to
Pr. 267 setting
0 to ±10V
0: 4 to 20mA
0 to ±5V
On
(initial value)
0 to ±10V
1: 0 to 5V
0 to ±10V
2: 0 to 10V
0 to ±5V
0 to ±5V
0 to ±10V
0 to ±5V
Pr. 73 Setting
Switch 2
OFF
OFF
ON
indicates the main speed setting)
Pr. 73
Setting
0
1
(initial value)
2
3
4
5
6
7
10
11
12
13
14
15
16
17
0
1
(initial value)
2
3
4
5
6
7
10
11
12
13
14
15
16
17
Terminal 4 Input
Specifications
Voltage input (0 to 10V)
Voltage input (0 to 5V)
Current input (0 to 20mA)
Compensation Input
Terminal and
Reversible
Compensation Method
Terminal 1
(Indicates that
Added compensation
a frequency
command
Terminal 2
Override
polarity is not
accepted.)
Terminal 1
Added compensation
Terminal 2
Override
Terminal 1
Added compensation
Terminal 1
(Indicates that
Added compensation
a frequency
command
Terminal 2
Override
polarity is not
accepted.)
Terminal 1
Added compensation
Terminal 2
Override
Terminal 1
Added compensation
Pr. 267 Setting
2
1
0 (initial value)
Polarity
No
signal of
negative
Yes
No
signal of
negative
Yes
⎯ : Invalid
Switch 1
OFF
OFF
ON