Faults history
Register
40501
Fault history 1
40502
Fault history 2
40503
Fault history 3
40504
Fault history 4
40505
Fault history 5
40506
Fault history 6
40507
Fault history 7
40508
Fault history 8
Data
Description
H00
No fault
H10
OC1
H11
OC2
H12
OC3
H20
OV1
H21
OV2
H22
OV3
H30
THT
H31
THM
H40
FIN
H50
IPF
H51
UVT
(7) Pr. 343 Communication error count
You can check the cumulative number of communication errors.
Parameters
343
CAUTION
The number of communication errors is temporarily stored into the RAM. As it is not stored into the EEPROM, performing
a power supply reset or inverter reset clears the value to 0.
(8) Output signal LF "alarm output (communication error warnings)"
During a communication error, the alarm signal (LF signal) is output by open collector output. The LF signal
can be assigned to the output terminal using any of Pr. 190 to Pr. 196 (output terminal function selection).
Master
Alarm data
Slave
Communication
Error count
(Pr.343)
OFF
Signal LF
CAUTION
Changing the terminal assignment using Pr. 190 to Pr. 196 (output terminal function selection) may affect the other functions. Make
setting after confirming the function of each terminal.
Definition
Fault code list
Data
Description
H52
ILF
H60
OLT
H70
BE
H80
GF
H81
LF
H90
OHT
H91
PTC
HA0
OPT
HA1
OP1
HB0
PE
HB1
PUE
HB2
RET
Setting Range
(Read only)
Alarm data
Normal data
Not increased
0
ON
Communication error count is increased in
synchronization with leading edge of LF signal
Communication operation and setting
Read/Write
Read/write
Read
Being 2 bytes in length, the data is stored as
Read
"H00
". Refer to the lowest 1 byte for the fault
Read
code.
Read
Performing write using the register 40501 batch-
Read
clears the faults history. Set any value as data.
Read
Read
Data
Description
Data
HB3
PE2
HF7
HC0
CPU
HFD
HC1
CTE
HC2
P24
HC4
CDO
HC5
IOH
HC6
SER
HC7
AIE
HE6
PID
HF1
E.1
HF5
E.5
HF6
E.6
Minimum Setting Range
1
Alarm data
Reply data
1
OFF
Turns off when normal data is received
Alarm data :
Remarks
Description
E.7
E.13
Initial Value
0
Normal data
Reply data
2
OFF
ON
Data resulting in
communication error.
4
219