Monitor display and monitor output signal
(3) How to calibrate the terminal FM when using the operation panel (FR-DU07)
Operation
1.
Confirmation of the RUN indication and
operation mode indication
2.
Press
to choose the parameter
setting mode.
3.
4.
Press
to read the present set value.
"
" (initial value) appears.
5.
Turn
to change it
to the setting value of "
6.
Press
to set.
7.
Turn
until
8.
Press
to display
9.
Turn
until
Set to C0 FM terminal calibration.
10.
Press
to enable setting.
11.
If the inverter is at a stop, (press
or
) to start the inverter.
(Motor needs not be connected.)
12.
Turn
to adjust the indicator needle
to the desired position.
13.
Press
. Setting is complete.
REMARKS
⋅ Calibration can also be made for external operation. Set the frequency in External operation mode, and make calibration in
the above procedure.
⋅ Calibration can be made even during operation.
⋅ For the operating procedure using the parameter unit (FR-PU04/FR-PU07), refer to the parameter unit instruction manual.
♦ Parameters referred to ♦
Pr. 54 FM terminal function selection
Pr. 55 Frequency monitoring reference
Pr.56 Current monitoring reference
Pr.158 AM terminal function selection
140
".
Flicker...Parameter setting complete!!
appears.
.
appears.
(
)
Flicker...Parameter setting complete!!
By turning
, you can read another parameter.
Press
to return to the
Press
twice to show the next parameter (
Refer to page 136
Refer to page 136
Refer to page 136
Refer to page 136
Display
(When Pr. 54=1)
The parameter
number read
previously appears.
C0 to C7
setting
is enabled.
The monitor set to Pr. 54 FM terminal
function selection is displayed.
+
Analog indicator
-
indication (step 8).
).