Motor Rotates In The Opposite Direction; Speed Greatly Differs From The Setting; Acceleration/Deceleration Is Not Smooth - Mitsubishi Electric FR-F720-0.75K to 110K Instruction Manual

Table of Contents

Advertisement

5.5.5

Motor rotates in the opposite direction

Check
points
Main
Phase sequence of output terminals U, V and W is
Circuit
incorrect.
The start signals (forward rotation, reverse rotation) are
connected improperly.
Input
The polarity of the frequency command is negative
signal
during the polarity reversible operation set by Pr. 73
Analog input selection.
5.5.6

Speed greatly differs from the setting

Check
points
Frequency setting signal is incorrectly input.
Input
signal
The input signal lines are affected by external EMI.
Pr. 1, Pr. 2, Pr. 18, calibration parameter C2 to C7 settings
Parameter
are improper.
Setting
Pr. 31 to Pr. 36 (frequency jump) settings are improper.
Load
Parameter
Stall prevention function is activated due to a heavy
load.
Setting
Motor
5.5.7

Acceleration/deceleration is not smooth

Check
points
Acceleration/deceleration time is too short.
Torque boost (Pr. 0, Pr. 46) setting is improper under V/F
control, so the stall prevention function is activated.
Parameter
The base frequency does not match the motor
Setting
characteristics.
Regeneration avoidance operation is performed
Load
Parameter
Stall prevention function is activated due to a heavy
load.
Setting
Motor
Possible Cause
Possible Cause
Possible Cause
Check first when you have a trouble
Countermeasures
Connect phase sequence of the output cables (terminal
U, V, W) to the motor correctly
Check the wiring. (STF: forward rotation , STR: reverse
rotation)
Check the polarity of the frequency command.
Countermeasures
Measure the input signal level.
Take countermeasures against EMI such as using
shielded wires for input signal lines.
Check the settings of Pr. 1 Maximum frequency, Pr. 2
Minimum frequency, Pr. 18 High speed maximum frequency.
Check the calibration parameter C2 to C7 settings.
Narrow down the range of frequency jump.
Reduce the load weight.
Set Pr. 22 Stall prevention operation level higher according
to the load. (Setting Pr. 22 too large may result in
frequent overcurrent trip (E.OC ).)
Check the capacities of the inverter and the motor.
Countermeasures
Increase acceleration/deceleration time.
Increase/decrease Pr. 0 Torque boost setting value by
0.5% increments to the setting.
For V/F control, set Pr. 3 Base frequency and Pr. 47 Second
V/F (base frequency).
If the frequency becomes unstable during regeneration
avoidance operation, decrease the setting of Pr. 886
Regeneration avoidance voltage gain.
Reduce the load weight.
Set Pr. 22 Stall prevention operation level higher according
to the load. (Setting Pr. 22 too large may result in
frequent overcurrent trip (E.OC ).)
Check the capacities of the inverter and the motor.
Refer
to
page
16
26
160
Refer
to
page
46
82
167
83
77
Refer
to
page
96
74
84
238
77
5
275